With refrigerant R290 and capacity from 35 to 73 kW Clivet
THUNDER (WiSAN-P) is the new air cooled reversible heat pump for outdoor installation with natural refrigerant, suitable for high water temperature production, equipped with inverter scroll compressors specifically designed for the use of R290, and inverter fans.
The WiSAN-P range from 35 to 73 kW, is the ideal solution to meet different kind of applications, from new installation to refurbishment, thanks to the full inverter technology, wide operating envelope and modular installation.
To guarantee always the highest safeness during the unit operation, some additional safety measures are included as standard on the whole range:
- Double leak detector sensors, installed one in the refrigerant circuit box and the second one in the electrical control box, to detect any possible refrigerant leakage;
- ATEX extraction fan in the refrigerant circuit box, activated whenever some leakage is detected (shutting at the same time off the compressors);
- Switch selector to autonomously activate the ATEX extraction fan for maximum safety during maintenance activities;
- Degasser filter for single unit can be provided as separate accessory to be installed on the hydraulic side, guaranteeing any leakage cannot enter the buliding.
- Full inverter technology with scroll compressors;
- High-temperature solution with modular approach;
- Natural and environmentally friendly refrigerant R290 - GWP = 3;
- High full load and seasonal efficiency with compact dimensions;
- Hot water up to 75Ѓ‹C and wide operating range from -20 C to +43 C;
- Three acoustic levels: standard, silenced and super-silenced;
- Modular design for up to 16 units in parallel (reduced installation space, enhanced system efficiency).
Sizes for THUNDER Air cooled reversible heat pump
Specifications:
|
Thunder SC 14.1 |
|
14.1 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
34,9 |
|
EER (EN 14511:2022) |
- |
2,84 |
|
SEER |
- |
5,36 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
39,9 |
|
COP (EN 14511:2022) |
- |
3,11 |
|
REFRIGERATION CIRCUITS |
Nr |
1 |
|
NUMBER OF COMPRESSORS |
Nr |
1 |
|
TYPE OF COMPRESSORS |
- |
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
4,90 |
|
ErP ENERGY CLASS W35 °C |
- |
A+++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,51 |
|
STANDARD AIRFLOW |
l/s |
11333 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
57 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
2400/1100/2250 |
|
WEIGHT |
kg |
709 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
Specifications:
|
Thunder SC 16.1 |
|
16.1 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
38,5 |
|
EER (EN 14511:2022) |
- |
2,81 |
|
SEER |
- |
5,20 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
45,2 |
|
COP (EN 14511:2022) |
- |
3,08 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
1 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
4,90 |
|
ErP ENERGY CLASS W35 °C |
- |
A+++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,45 |
|
STANDARD AIRFLOW |
l/s |
11333 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
57 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
2400/1100/2250 |
|
WEIGHT |
kg |
709 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
Specifications:
|
Thunder SC 18.1 |
|
18.1 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
49,9 |
|
EER (EN 14511:2022) |
- |
2,58 |
|
SEER |
- |
4,73 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
55,1 |
|
COP (EN 14511:2022) |
- |
3,19 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
1 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
4,50 |
|
ErP ENERGY CLASS W35 °C |
- |
A++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,29 |
|
STANDARD AIRFLOW |
l/s |
11333 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
59 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
2400/1100/2250 |
|
WEIGHT |
kg |
757 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
Specifications:
|
Thunder SC 19.1 |
|
19.1 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
54,0 |
|
EER (EN 14511:2022) |
- |
2,46 |
|
SEER |
- |
4,58 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
61,5 |
|
COP (EN 14511:2022) |
- |
3,13 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
1 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
4,50 |
|
ErP ENERGY CLASS W35 °C |
- |
A++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,23 |
|
STANDARD AIRFLOW |
l/s |
11333 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
59 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
2400/1100/2250 |
|
WEIGHT |
kg |
757 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
Specifications:
|
Thunder SC 20.1 |
|
20.1 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
58,2 |
|
EER (EN 14511:2022) |
- |
2,35 |
|
SEER |
- |
4,36 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
68,5 |
|
COP (EN 14511:2022) |
- |
2,92 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
1 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
4,50 |
|
ErP ENERGY CLASS W35 °C |
- |
A++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,15 |
|
STANDARD AIRFLOW |
l/s |
11333 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
60 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
2400/1100/2250 |
|
WEIGHT |
kg |
757 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
Specifications:
|
Thunder SC 25.2 |
|
25.2 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
67,8 |
|
EER (EN 14511:2022) |
- |
2,86 |
|
SEER |
- |
5,47 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
78,6 |
|
COP (EN 14511:2022) |
- |
3,14 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
2 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
10,00 |
|
ErP ENERGY CLASS W35 °C |
- |
A+++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,7 |
|
STANDARD AIRFLOW |
l/s |
17083 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
59 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
3400/1100/2250 |
|
WEIGHT |
kg |
1021 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |
| Recommended price with VAT: 72 407.40 BGN |
Specifications:
|
Thunder SC 30.2 |
|
30.2 |
|
|
|
|
|
COOLING CAPACITY A35°/W7° (EN 14511:2022) |
kW |
72,7 |
|
EER (EN 14511:2022) |
- |
2,64 |
|
SEER |
- |
5,30 |
|
HEATING CAPACITY А7°/W45° (EN 14511:2022) |
kW |
85,9 |
|
COP (EN 14511:2022) |
- |
3,01 |
|
REFRIGERATION CIRCUITS |
бр. |
1 |
|
NUMBER OF COMPRESSORS |
бр. |
2 |
|
TYPE OF COMPRESSORS |
|
SCROLL INVERTER |
|
REFRIGERANT |
- |
R290 |
|
REFRIGERANT QUANTITY |
kg |
10,00 |
|
ErP ENERGY CLASS W35 °C |
- |
A+++ |
|
SCOP - SEASONAL COEFFICIENT OF PERFORMANCE |
- |
4,54 |
|
STANDARD AIRFLOW |
l/s |
17083 |
|
POWER SUPPLY (VOLTAGE/FREQUENCY/PHASES) |
V/Hz/n* |
400/50/3 |
|
SOUND PRESSURE LEVEL |
dB(A) |
60 |
|
DIMENSIONS (LENGTH/WIDTH/HEIGHT) |
mm |
3400/1100/2250 |
|
WEIGHT |
kg |
1021 |
|
OPERATING RANGE |
°C |
-20 ÷ 43 |